Home Categories Send inquiry

High Efficiency 100kw 250kw 500kw 630kw Hybrid Solar Inverter for Commercial Industrial

Datasheet ATESS PCS50 ATESS PCS100 ATESS PCS250 ATESS PCS500 ATESS PCS630
AC(Grid-connected)          
Apparent power Rated power Rated voltage Rated current Voltage range Rated frequency Frequency range THDI PF AC connection 55kVA 50KW 400V 72A 310V-450V 50/60Hz 45-55/55-65Hz <3% 0.8lagging-0.8leading 3/N/PE 110kVA 100KW 400V 144A 310V-450V 50/60Hz 45-55/55-65Hz <3% 0.8lagging-0.8leading 3/N/PE 275kVA 250KW 400V 361A 310V-450V 50/60Hz 45-55/55-65Hz <3% 0.8lagging-0.8leading 3/N/PE 550kVA 500KW 400V 722A 310V-450V 50/60Hz 45-55/55-65Hz <3% 0.8lagging-0.8leading 3/PE 693kVA 630KW 400V 909A 310V-450V 50/60Hz 45-55/55-65Hz <3% 0.8lagging-0.8leading 3/PE
AC(off-grid)          
Apparent power Rated power Rated voltage Rated current THDU Rated frequency Overload capability 55kVA 50KW 400V 72A ≤2% linear 50/60Hz 110%- 10min 120%- 1min 110kVA 100KW 400V 144A ≤2% linear 50/60Hz 110%- 10min 120%- 1min 275kVA 250KW 400V 361A ≤2% linear 50/60Hz 110%- 10min 120%- 1min 550kVA 500KW 400V 722A ≤2% linear 50/60Hz 110%- 10min 120%- 1min 693kVA 630KW 400V 909A ≤2% linear 50/60Hz 110%- 10min 120%- 1min
DC(battery)          
Rated power Current regulation Voltage regulatoin Voltage ripple Current ripple Rated voltage Voltage range Rated current 50kW ±1% ±1% <3% <2% 600VDC 500V-820V 84A 100kW ±1% ±1% <3% <2% 600VDC 500V-820V 167A 250kW ±1% ±1% <3% <2% 600VDC 500V-820V 417A 500kW ±1% ±1% <3% <2% 700VDC 600V-900V 714A 630kW ±1% ±1% <3% <2% 700VDC 600V-900V 900A
General Information          
Maximum efficiency Protection degree Noise emission Environment temperature Cooling Relative humidity Maximum altitude Dimension(W/H/D) Weight Build-in transformer Transfer between on/off grid 95.50% IP20 <65dB(A)@1m -25°C...+55°C Forced-air           0-95% non-condensing 6000m (derate above 3000m) 600/1630/800mm 450kg Yes Manual(default) Automatic(optional) ≤ 10ms 97. 10% IP20 <65dB(A)@1m -25°C...+55°C Forced-air           0-95% non-condensing 6000m (derate above 3000m) 1100/1890/850mm 820kg Yes Manual(default) Automatic(optional) ≤ 10ms 97.30% IP20 <65dB(A)@1m -25°C...+55°C Forced-air           0-95% non-condensing 6000m (derate above 3000m) 1600/2080/850mm 1465kg Yes Manual(default) Automatic(optional) ≤ 10ms 98.50% IP20 <65dB(A)@1m -25°C...+55°C Forced-air           0-95% non-condensing 6000m (derate above 3000m) 1200/1900/800mm 900Kg NO Manual(default) Automatic(optional) ≤ 10ms 98.50% IP20 <65dB(A)@1m -25°C...+55°C Forced-air           0-95% non-condensing 6000m (derate above 3000m) 1200/1900/800mm 900Kg NO Manual(default) Automatic(optional) ≤ 10ms
Communication          
Display Communication interface Touch screen RS485/CAN Touch screen RS485/CAN Touch screen RS485/CAN Touch screen RS485/CAN Touch screen RS485/CAN